Mineral insulated sensing insert with connection head

pro-img

Mineral insulated sensing insert with connection head

T-M-N / W-M-N, according to DIN 43721 (datasheet 12)

Features
  • temperature range -200…+1200 °C
  • Pt100 or thermocouple (TC)
  • standard materials AISI 316L or INCONEL 600, others on request
  • Pt100, accuracy class A, as a standard, more accurate on request
  • TC, class 1 as a standard
  • MI-construction, bendable and vibration proof
  • fixing with welded flanges, adjustable flange or compression fitting
  • adjustable immersion length due to sliding mounting
  • tailored solutions according to specific needs
  • ATEX-version, Ex i and Ex d available.
Typical applications
  • Energy and power plant technology
  • Process industry
  • Chemical industry
  • Machinery, plant and vessel construction.

Drawing

Technical data

MI-wire material AISI 316L, max. temp. +550 °C, temporarily +600 °C.
INCONEL 600, max. +1100 °C, temporarily +1200 °C.
Tolerances Pt100 (EN-60751) A, tolerance +/- 0,15 + 0,002 x t, operating temperature -100…+450 °C
B, tolerance +/- 0,3 + 0,005 x t, operating temperature -196…+600 °C
B 1/3 DIN, tolerance +/- 1/3 x (0,3 + 0,005 x t), operating temperature -196…+600 °C
B 1/10 DIN, tolerance +/- 1/10 x (0,3 + 0,005 x t), operating temperature -196…+600 °C
Tolerances TC (EN-60584-2) Type J, tolerance class 1 = -40…375 °C +/- 1,5 °C, 375…750 °C +/- 0,004 x t
Type K and N, tolerance class 1 = -40…375 °C +/- 1,5 °C, 375…1000 °C +/- 0,004 x t
Temperature range Pt100 -200…+550 °C, depending on application and material
Temperature range TC -40…+1200 °C depending on thermocouple type                 TC = thermocouple
Approvals ATEX, GOST-R, METROLOGICAL PATTERN APPROVAL, ROSTECHNADZOR
Quality certificate ISO 9001:2008 issued by DNV
IP-class IP65, higher IP-class on request

Connections

Installation example

Connection heads

Version D/H with quick release clip and blue epoxy lack finish is our standard, but for certain applications other types are better suited.

Download Format
Datasheet-EN-12 .pdf
+ Drawing

Drawing

+ Technical data

Technical data

MI-wire material AISI 316L, max. temp. +550 °C, temporarily +600 °C.
INCONEL 600, max. +1100 °C, temporarily +1200 °C.
Tolerances Pt100 (EN-60751) A, tolerance +/- 0,15 + 0,002 x t, operating temperature -100…+450 °C
B, tolerance +/- 0,3 + 0,005 x t, operating temperature -196…+600 °C
B 1/3 DIN, tolerance +/- 1/3 x (0,3 + 0,005 x t), operating temperature -196…+600 °C
B 1/10 DIN, tolerance +/- 1/10 x (0,3 + 0,005 x t), operating temperature -196…+600 °C
Tolerances TC (EN-60584-2) Type J, tolerance class 1 = -40…375 °C +/- 1,5 °C, 375…750 °C +/- 0,004 x t
Type K and N, tolerance class 1 = -40…375 °C +/- 1,5 °C, 375…1000 °C +/- 0,004 x t
Temperature range Pt100 -200…+550 °C, depending on application and material
Temperature range TC -40…+1200 °C depending on thermocouple type                 TC = thermocouple
Approvals ATEX, GOST-R, METROLOGICAL PATTERN APPROVAL, ROSTECHNADZOR
Quality certificate ISO 9001:2008 issued by DNV
IP-class IP65, higher IP-class on request